8.7 Alternative foundation designs

The foundation design should comply with 8.6 and with one of the following alternatives.

8.7.1 Foundations with no ground insulation

The foundation depth should be:

  • at the walls, at least Hf;
  • near the corners and at limited unheated parts for a distance Lc from these places, at least the greater depth Hfc (if Fd > 30 000 K·h);

where the values of Hf, Hfc and Lc are given in Table 3 as a function of the design freezing index.

Table 3 — Foundation depth for slab-on-ground floor without ground insulation
Fd
K·h
Hf
m
Hfc
m
Lc
m
Fd ≤ 30 000 0,35 0,35
30 000 < Fd ≤ 35 000 0,40 0,60 1,0
35 000 < Fd ≤ 40 000 0,50 0,80 1,0
40 000 < Fd ≤ 45 000 0,60 1,00 1,5
45 000 < Fd ≤ 50 000 0,75 1,30 1,5
50 000 < Fd ≤ 55 000 0,90 1,60 1,5
55 000 < Fd ≤ 60 000 1,10 1,80 2,0
60 000 < Fd ≤ 65 000 1,30 2,00 2,0
65 000 < Fd ≤ 70 000 1,50 2,20 2,5

 

8.7.2 Ground insulation only at corners

If Fd 30 000 K·h, ground insulation is not required.

For greater values of Fd, the foundation depth shall be at least Hf all round the building, and ground insulation shall be used near corners and at limited unheated parts for a distance Lc from these places, where the values of Hf and Lc are given in Table 4.

The thermal resistance of the ground insulation shall be at least 1,0 m2·K/W, and its width shall be bgc, values of bgc being given in Table 4. See also Figure 3.

Table 4 — Foundation depth and corner insulation for slab-on-ground floor
Fd
K·h
Hf
m
bgc
m
Lc
m
Fd ≤ 30 000 0,35
30 000 < Fd ≤ 35 000 0,40 0,50 1,0
35 000 < Fd ≤ 40 000 0,50 0,50 1,0
40 000 < Fd ≤ 45 000 0,60 0,50 1,5
45 000 < Fd ≤ 50 000 0,75 0,60 1,5
50 000 < Fd ≤ 55 000 0,90 0,80 1,5
55 000 < Fd ≤ 60 000 1,10 0,80 2,0
60 000 < Fd ≤ 65 000 1,30 0,80 2,0
65 000 < Fd ≤ 70 000 1,50 1,00 2,5

 

8.7.3 Ground insulation all round the building

If Fd 30 000 K·h, ground insulation is not required.

For greater values of Fd, the foundation depth may be reduced to not less than 0,4 m by placing ground insulation all round the building.

If Fd > 30 000 K·h, ground insulation is necessary near corners and at limited unheated parts, for a distance Lc from these places as given in Table 5. Select an appropriate combination of thermal resistance, Rgc, and width, bgc, of ground insulation near the corners using Figure 4, according to the value of Fd.

If Fd > 37 500 K·h, ground insulation is also necessary along the walls. Select an appropriate combination of thermal resistance, Rgw, and width, bgw, of ground insulation along the walls using Figure 5, according to the value of Fd. Then use Figure 4 to determine the greater ground insulation needed near the corners and unheated parts. The corner insulation applies for a distance Lc as given in Table 5.

See also Figure 3.

Width of ground insulation

Key

  • 1 Limited unheated part (store room, porch etc)
Figure 3 — Width of ground insulation

 

Width and thermal resistance of ground insulation at corners and limited unheated parts, for slab-on-ground floor with Hf 0,4 m

Key

1 minimum bgc 3 Width of ground insulation at corners, bgc
2 minimum Rgc 4 Thermal resistance of ground insulation at corners, Rgc
Figure 4 — Width and thermal resistance of ground insulation at corners and limited unheated parts, for slab-on-ground floor with Hf 0,4 m
Width and thermal resistance of ground insulation along walls, for slab-on-ground floor with Hf 0,4 m

Key

1 minimum bgw 3 Width of ground insulation along walls, bgw
2 minimum Rgw 4 Thermal resistance of ground insulation along walls, Rgw
Figure 5 — Width and thermal resistance of ground insulation along walls, for slab-on-ground floor with Hf 0,4 m
Table 5 — Length of corner insulation
Fd
K·h
Lc
m
Fd 30 000
30 000 < Fd ≤ 35 000 1,0
35 000 < Fd ≤ 40 000 1,0
40 000 < Fd ≤ 45 000 1,5
45 000 < Fd ≤ 50 000 1,5
50 000 < Fd ≤ 55 000 1,5
55 000 < Fd ≤ 60 000 2,0
60 000 < Fd ≤ 65 000 2,0
65 000 < Fd ≤ 70 000 2,5

 

8.8 Buildings with low internal temperature

For poorly heated buildings with 5° C ≤ θi,m < 17 °C, the values in 8.7.3 may be used if Hf is at least 0,6 m instead of 0,4 m.

Alternatively increase the values of Hf in Table 3 or Table 4 by 0,2 m.

If θi,m <5 °C in any month, the frost protection of the foundations shall be designed as for unheated buildings (see clause 10).

ISO 13793-2001 Thermal performance of buildings Thermal design of foundations to avoid frost heave